Electronic ballast Tridonic PCA 2x21/39W DALI ECO 22185102
Specification
-
VAT:23,00%
-
UPC Code:9006210264806
-
Symbol:22176177
Product Description
Tridonic is a company specializing in the production of advanced lighting solutions, including the production of ballasts. Tridonic ballasts are known for their high quality and innovative technological solutions, which are used in various lighting systems.
Electronic ballast Tridonic 2x21/39W T5 EXCEL 22176177
- World first: the first processor-controlled ballast with X technology
- Support for T5 lamps of the same length (e.g. FH 28W / FQ 54W)
- Automatic lamp detection and operation with appropriate parameters
- Average lifespan = 50,000 hours (at max. ambient temperature and failure rate ? 0.2% per 1,000 operating hours)
- Dimming range from 1% to 100%
- Lamp-friendly warm start in 0.5 s for AC and 0.2 s for DC
- Standby power consumption < 0.5W
- Interference-free, precise control via digital signal (DSI), switchDIM or DALI (Digital Addressable Lighting Interface)
- Fully digital lamp management for flash-free starting at any dimming level
- Operating frequency ~40–100 kHz
- Integrated SMART interface
- Intelligent Voltage Guard (overvoltage indication and switch-off at too low voltage)
- Intelligent Temperature Guard (overheating protection)
- Automatically activated, adjustable emergency light level for DC and rectified AC voltage
- SMART Heating Concept – optimal heating of filaments at every dimming level and disconnection of electrodes at approx. 90% dimming level for maximum energy savings
- plugADDRESSING – easy addressing of devices
Technical data
- For T5 fluorescent lamps
- 2x21W
- 2x39W
- Protection type IP20
- Dimensions [mm]: L-425, D-415, weight - 0.35kg
Lamp start characteristics:
- Warm start
- Start time: 0.5 s with AC power
- Start time: 0.2 s with DC power
Ability to start at any dimming level
AC operation:
- Mains voltage: 220–240 V, 50/60 Hz
- Voltage range: 198–264 V, 50/60 Hz (including safety tolerance ±10%), 202–254 V, 50/60 Hz (including efficiency tolerance +6% / -8%)
DC operation:
- Voltage: 220–240 V, 0 Hz
- Voltage range for reliable lamp start: 198–280 V, 0 Hz
- Operating voltage range: 176–280 V, 0 Hz
Application in emergency lighting:
Compliance with EN 50172 for emergency lighting installations
Compliance with EN 61347-2-3, Annex J, for emergency luminaires
Statecznik jest przystosowany do pracy zarówno z napięciem stałym (DC), jak i pulsującym napięciem stałym (pulsed DC).
For the ballast to function properly with pulsating DC voltage, maintaining the correct polarity is absolutely necessary.